| A security issue was found in the IPv6 stack in the Micro850 and Micro870 controllers when the controllers received multiple malformed packets during fuzzing. The controllers will go into recoverable fault with fault code 0xFE60. To recover the controller, clear the fault. |
| A security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault. |
| A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault. |
| A security issues exists within Studio 5000 Logix Designer due to unsafe handling of environment variables. If the specified path lacks a valid file, Logix Designer crashes; However, it may be possible to execute malicious code without triggering a crash. |
| An improper authorization vulnerability exists in the Rockwell Automation affected products that could allow an unauthorized user to sign in. While removal of all role mappings is unlikely, it could occur in the case of unexpected or accidental removal by the administrator. If exploited, an unauthorized user could access data they previously but should no longer have access to. |
| A security issue was discovered within FactoryTalk® ViewPoint, allowing unauthenticated attackers to achieve XXE. Certain SOAP requests can be abused to perform XXE, resulting in a temporary denial-of-service. |
| Studio 5000 Logix Designer 30.01.00 contains an unquoted service path vulnerability in the FactoryTalk Activation Service that allows local users to potentially execute code with elevated privileges. Attackers can exploit the unquoted path in C:\Program Files (x86)\Rockwell Software\FactoryTalk Activation\ to inject malicious code that would execute with LocalSystem permissions. |
| A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IY8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle. |
| A security issue exists within 432ES-IG3 Series A, which affects GuardLink® EtherNet/IP Interface, resulting in denial-of-service. A manual power cycle is required to recover the device. |
| A security issue was discovered in DataMosaix Private Cloud, allowing users with low privilege to perform sensitive database operations through exposed API endpoints. |
| A security issue exists within the Studio 5000 Logix Designer add-on profile (AOP) for the ArmorStart Classic distributed motor controller, resulting in denial-of-service. This vulnerability is possible due to the input of invalid values into Component Object Model (COM) methods. |
| CVE-2024-6078 IMPACT
An improper authentication vulnerability exists in the affected product, which could allow a malicious user to generate cookies for any user ID without the use of a username or password. If exploited, a malicious user could take over the account of a legitimate user. The malicious user would be able to view and modify data stored in the cloud. |
| A security issue in the runtime event system allows unauthenticated connections to receive a reusable API token. This token is broadcasted over a WebSocket and can be intercepted by any local client listening on the connection. |
| A denial-of-service security issue in the affected product. The security issue stems from a fault occurring when a crafted CIP unconnected explicit message is sent. This can result in a major non-recoverable fault. |
| A Remote
Code Execution vulnerability exists in the affected product. The vulnerability requires
a high level of permissions and exists due to improper input validation resulting
in the possibility of a malicious Updated Agent being deployed. |
| A denial-of-service security issue in the affected product. The security issue occurs when a malformed CIP forward open message is sent. This could result in a major nonrecoverable fault a restart is required to recover. |
| Multiple denial-of-service vulnerabilities exist in the affected product. These issues can be triggered through various crafted inputs, including malformed Class 3 messages, memory leak conditions, and other resource exhaustion scenarios. Exploitation may cause the device to become unresponsive and, in some cases, result in a major nonrecoverable fault. Recovery may require a restart. |
| A security issue was discovered within Verve Asset Manager allowing unauthorized read-only users to read, update, and delete users via the API. |
| A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IF8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle. |
| A security issue exists due to the web-based debugger agent enabled on Rockwell Automation ControlLogix® Ethernet Modules. If a specific IP address is used to connect to the WDB agent, it can allow remote attackers to perform memory dumps, modify memory, and control execution flow. |