| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| A vulnerability has been identified in COMOS V10.6 (All versions < V10.6.1), COMOS V10.6 (All versions < V10.6.1), JT Bi-Directional Translator for STEP (All versions), NX V2412 (All versions < V2412.8900 with Cloud Entitlement (bundled as NX X)), NX V2506 (All versions < V2506.6000 with Cloud Entitlement (bundled as NX X)), Simcenter 3D (All versions < V2506.6000 with Cloud Entitlement (bundled as Simcenter X Mechanical)), Simcenter Femap (All versions < V2506.0002 with Cloud Entitlement (bundled as Simcenter X Mechanical)), Simcenter Studio (All versions < V2506.0001), Simcenter System Architect (All versions < V2506.0001), Tecnomatix Plant Simulation (All versions < V2504.0007). The SALT SDK is missing server certificate validation while establishing TLS connections to the authorization server. This could allow an attacker to perform a man-in-the-middle attack. |
| A vulnerability has been identified in SENTRON 7KM PAC3200 (All versions). Affected devices only provide a 4-digit PIN to protect from administrative access via Modbus TCP interface. Attackers with access to the Modbus TCP interface could easily bypass this protection by brute-force attacks or by sniffing the Modbus clear text communication. |
| A vulnerability has been identified in SIMATIC STEP 7 Safety V16 (All versions < V16 Update 7), SIMATIC STEP 7 Safety V17 (All versions < V17 Update 7), SIMATIC STEP 7 Safety V18 (All versions < V18 Update 2), SIMATIC STEP 7 V16 (All versions < V16 Update 7), SIMATIC STEP 7 V17 (All versions < V17 Update 7), SIMATIC STEP 7 V18 (All versions < V18 Update 2), SIMATIC WinCC Unified V16 (All versions < V16 Update 7), SIMATIC WinCC Unified V17 (All versions < V17 Update 7), SIMATIC WinCC Unified V18 (All versions < V18 Update 2), SIMATIC WinCC V16 (All versions < V16.7), SIMATIC WinCC V17 (All versions < V17.7), SIMATIC WinCC V18 (All versions < V18 Update 2), SIMOCODE ES V16 (All versions < V16 Update 7), SIMOCODE ES V17 (All versions < V17 Update 7), SIMOCODE ES V18 (All versions < V18 Update 2), SIMOTION SCOUT TIA V5.4 SP1 (All versions), SIMOTION SCOUT TIA V5.4 SP3 (All versions), SIMOTION SCOUT TIA V5.5 SP1 (All versions), SINAMICS Startdrive V16 (All versions), SINAMICS Startdrive V17 (All versions), SINAMICS Startdrive V18 (All versions), SIRIUS Safety ES V17 (All versions < V17 Update 7), SIRIUS Safety ES V18 (All versions < V18 Update 2), SIRIUS Soft Starter ES V17 (All versions < V17 Update 7), SIRIUS Soft Starter ES V18 (All versions < V18 Update 2), Soft Starter ES V16 (All versions < V16 Update 7), TIA Portal Cloud V3.0 (All versions < V18 Update 2). Affected applications do not properly restrict the .NET BinaryFormatter when deserializing hardware configuration profiles. This could allow an attacker to cause a type confusion and execute arbitrary code within the affected application.
This is the same issue that exists for .NET BinaryFormatter https://docs.microsoft.com/en-us/visualstudio/code-quality/ca2300. |
| A vulnerability has been identified in APOGEE PXC Series (BACnet) (All versions), APOGEE PXC Series (P2 Ethernet) (All versions), TALON TC Series (BACnet) (All versions). Affected devices connected to the network allow unrestricted access to sensitive files, such as databases. This could allow an attacker to download encrypted .db file containing passwords. |
| A vulnerability has been identified in RUGGEDCOM RST2228 (All versions < V5.9.0), RUGGEDCOM RST2228P (All versions < V5.9.0). The web server of the affected systems leaks the MACSEC key in clear text to a logged in user. An attacker with the credentials of a low privileged user could retrieve the MACSEC key and access (decrypt) the ethernet frames sent by authorized recipients. |
| A vulnerability has been identified in Mendix Encryption (All versions >= V10.0.0 < V10.0.2). Affected versions of the module define a specific hard-coded default value for the EncryptionKey constant, which is used in projects where no individual EncryptionKey was specified.
This could allow to an attacker to decrypt any encrypted project data, as the default encryption key can be considered compromised. |
| A vulnerability has been identified in SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0) (All versions < V2.4.24), SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0) (All versions < V2.4.24), SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0) (All versions < V2.4.24), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0) (All versions < V2.4.24), SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0) (All versions < V2.4.24), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0) (All versions < V2.4.24). Affected devices do not properly authenticate configuration connections. This could allow an unauthenticated remote attacker to access the configuration data. |
| A vulnerability has been identified in SIMATIC S7-PLCSIM V16 (All versions), SIMATIC S7-PLCSIM V17 (All versions), SIMATIC STEP 7 Safety V16 (All versions), SIMATIC STEP 7 Safety V17 (All versions < V17 Update 8), SIMATIC STEP 7 Safety V18 (All versions < V18 Update 5), SIMATIC STEP 7 V16 (All versions), SIMATIC STEP 7 V17 (All versions < V17 Update 8), SIMATIC STEP 7 V18 (All versions < V18 Update 5), SIMATIC WinCC Unified V16 (All versions), SIMATIC WinCC Unified V17 (All versions < V17 Update 8), SIMATIC WinCC Unified V18 (All versions < V18 SP5), SIMATIC WinCC V16 (All versions), SIMATIC WinCC V17 (All versions < V17 Update 8), SIMATIC WinCC V18 (All versions < V18 SP5), SIMOCODE ES V16 (All versions), SIMOCODE ES V17 (All versions < V17 Update 8), SIMOCODE ES V18 (All versions), SIMOTION SCOUT TIA V5.4 SP1 (All versions), SIMOTION SCOUT TIA V5.4 SP3 (All versions), SIMOTION SCOUT TIA V5.5 SP1 (All versions), SINAMICS Startdrive V16 (All versions), SINAMICS Startdrive V17 (All versions), SINAMICS Startdrive V18 (All versions), SIRIUS Safety ES V17 (TIA Portal) (All versions < V17 Update 8), SIRIUS Safety ES V18 (TIA Portal) (All versions), SIRIUS Soft Starter ES V17 (TIA Portal) (All versions < V17 Update 8), SIRIUS Soft Starter ES V18 (TIA Portal) (All versions), TIA Portal Cloud V16 (All versions), TIA Portal Cloud V17 (All versions < V4.6.0.1), TIA Portal Cloud V18 (All versions < V4.6.1.0). Affected products do not properly sanitize user-controllable input when parsing user settings. This could allow an attacker to cause a type confusion and execute arbitrary code within the affected application. |
| A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). Affected SIMATIC RTLS Locating Manager Track Viewer Client do not properly protect credentials that are used to authenticate to the server. This could allow an authenticated local attacker to extract the credentials and use them to escalate their access rights from the Manager to the Systemadministrator role. |
| A vulnerability has been identified in COMOS V10.6 (All versions < V10.6.1), COMOS V10.6 (All versions < V10.6.1), NX V2412 (All versions < V2412.8700), NX V2506 (All versions < V2506.6000), Simcenter 3D (All versions < V2506.6000), Simcenter Femap (All versions < V2506.0002), Solid Edge SE2025 (All versions < V225.0 Update 10), Solid Edge SE2026 (All versions < V226.0 Update 1). The IAM client in affected products is missing server certificate validation while establishing TLS connections to the authorization server. This could allow an attacker to perform a man-in-the-middle attack. |
| A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants) (All versions < V2.0.2), SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants) (All versions < V2.0.2). Affected controllers are vulnerable to capture-replay in the communication with the engineering software. This could allow an on-path attacker between the engineering software and the controller to execute any previously recorded commands at a later time (e.g. set the controller to STOP), regardless whether or not the controller had a password configured. |
| A vulnerability has been identified in Tecnomatix Plant Simulation V2302 (All versions < V2302.0015), Tecnomatix Plant Simulation V2404 (All versions < V2404.0004). The affected applications contain a stack based overflow vulnerability while parsing specially crafted SPP files. This could allow an attacker to execute code in the context of the current process. |
| A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants) (All versions < V2.0.3), SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants) (All versions < V2.0.3). The web server interface of affected devices improperly processes incoming malformed HTTP traffic at high rate. This could allow an unauthenticated remote attacker to force the device entering the stop/defect state, thus creating a denial of service condition. |
| A vulnerability has been identified in SIMATIC Energy Manager Basic (All versions < V7.5), SIMATIC Energy Manager PRO (All versions < V7.5), SIMATIC IPC DiagBase (All versions), SIMATIC IPC DiagMonitor (All versions), SIMIT V10 (All versions), SIMIT V11 (All versions < V11.1). Unified Automation .NET based OPC UA Server SDK before 3.2.2 used in Siemens products are affected by a similar vulnerability as documented in CVE-2023-27321 for the OPC Foundation UA .NET Standard implementation. A successful attack may lead to high load situation and memory exhaustion, and may block the server. |
| A vulnerability has been identified in Tecnomatix Plant Simulation V2302 (All versions < V2302.0011). The affected application contains an out of bounds write past the end of an allocated buffer while parsing a specially crafted MODEL file. This could allow an attacker to execute code in the context of the current process. (ZDI-CAN-22974) |
| A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). Affected applications do not properly release memory that is allocated when handling specifically crafted incoming packets. This could allow an unauthenticated remote attacker to cause a denial of service condition by crashing the service when it runs out of memory. The service is restarted automatically after a short time. |
| A vulnerability has been identified in Industrial Edge Management Pro (All versions < V1.9.5), Industrial Edge Management Virtual (All versions < V2.3.1-1). Affected components do not properly validate the device tokens. This could allow an unauthenticated remote attacker to impersonate other devices onboarded to the system. |
| A vulnerability has been identified in Opcenter Quality (All versions < V2406), Opcenter RDnL (All versions < V2410), SIMATIC PCS neo V4.0 (All versions), SIMATIC PCS neo V4.1 (All versions < V4.1 Update 2), SIMATIC PCS neo V5.0 (All versions < V5.0 Update 1), SINEC NMS (All versions), SINEMA Remote Connect Client (All versions < V3.2 SP3), Totally Integrated Automation Portal (TIA Portal) V16 (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions < V17 Update 8), Totally Integrated Automation Portal (TIA Portal) V18 (All versions < V18 Update 5), Totally Integrated Automation Portal (TIA Portal) V19 (All versions < V19 Update 3). Affected products contain a heap-based buffer overflow vulnerability in the integrated UMC component. This could allow an unauthenticated remote attacker to execute arbitrary code. |
| A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). The affected application does not properly limit the size of specific logs. This could allow an unauthenticated remote attacker to exhaust system resources by creating a great number of log entries which could potentially lead to a denial of service condition. A successful exploitation requires the attacker to have access to specific SIMATIC RTLS Locating Manager Clients in the deployment. |
| A vulnerability has been identified in RUGGEDCOM ROX MX5000 (All versions < V2.16.5), RUGGEDCOM ROX MX5000RE (All versions < V2.16.5), RUGGEDCOM ROX RX1400 (All versions < V2.16.5), RUGGEDCOM ROX RX1500 (All versions < V2.16.5), RUGGEDCOM ROX RX1501 (All versions < V2.16.5), RUGGEDCOM ROX RX1510 (All versions < V2.16.5), RUGGEDCOM ROX RX1511 (All versions < V2.16.5), RUGGEDCOM ROX RX1512 (All versions < V2.16.5), RUGGEDCOM ROX RX1524 (All versions < V2.16.5), RUGGEDCOM ROX RX1536 (All versions < V2.16.5), RUGGEDCOM ROX RX5000 (All versions < V2.16.5). The 'Log Viewers' tool in the web interface of affected devices is vulnerable to command injection due to missing server side input sanitation. This could allow an authenticated remote attacker to execute the 'tail' command with root privileges and disclose contents of all files in the filesystem. |